Rated fuse currents of 3 phase motors
|
Motor Rating |
415V |
kW |
HP |
Cosj
|
h
%
|
Rated
Motor
Current
A |
Fuse starting D.O.L
A |
Y/D
A |
0.06
0.09 0.12 0.18 0.25 0.37 0.55 0.75 1.1 1.5 2.2 3 4 5.5 7.5 11 15 18.5 22 30 37 45 55 75 90 110 132 160 200 250 315 400 450 500 560 630
|
0.08
0.12 0.16 0.25 0.33 0.5 0.75 1 1.5 2 3 4 5.5 7.5 10 15 20 25 30 40 50 60 75 100 125 150 175 220 270 350 422 536 603 670 750 845
|
0.7
0.7 0.7 0.7 0.7 0.72 0.75 0.79 0.81 0.81 0.81 0.82 0.82 0.82 0.82 0.84 0.84 0.84 0.84 0.85 0.86 0.86 0.86 0.86 0.86 0.86 0.87 0.87 0.87 0.87 0.87 0.88 0.88 0.88 0.88 0.88
|
58
60 60 62 62 66 69 74 74 74 78 80 83 86 87 87 88 88 92 92 92 93 93 94 94 94 95 95 95 95 96 96 96 97 97 97
|
0.21
0.30 0.40 0.58 0.8 1.1 1.5 1.8 2.6 3.5 4.8 6.4 8.2 10.9 14.6 20.9 28.2 35 40 53 65 78 96 129 155 189 222 269 337 421 525 - - - - -
|
2
2 2 2 4 4 6 6 10 16 16 20 20 25 35 50 80 80 80 100 125 125 160 250 250 315 355 355 450 500 630 - - - - -
|
2
2 2 2 2 2 4 4 6 10 10 16 16 20 25 32 40 50 50 80 80 80 100 160 160 200 250 315 355 450 560 - - - - -
|
(Approximate figures for squirrel-cage motors).
Minimum fuse size for short-circuit protection of 3-phase motors.
The maximum size is determined by the requirements of the switchgear or overload relay
The rated motor currents are for standard 1500 r.p.m. 3-phase enclosed ventilated and totally enclosed fan-cooled motors.
D.O.L. starting : maximum starting current 6 x rated motor current. Maximum starting time : 5 s.
Y/D starting : maximum starting current 2 x rated motor current. Maximum starting time : 15 s.
set overload relay in the phase lead to 0.58 x rated motor current.
Rated fuse currents for Y/D starting are also valid for 3-phase motors with slip-ring rotors.
For higher rated currents, starting currents / longer starting times, larger fuses will be required.
Table is valid for 'slow' / 'gL' fuses (DIN VDE 0636)
For NH fuses with aM characteristic, fuses = rated current selected.
|
|