Motor Currents Print

Rated fuse currents of 3 phase motors

Motor Rating 415V

kW

HP

Cosj

h
%

Rated
Motor
Current
A

Fuse starting D.O.L
A

Y/D
A

0.06
0.09
0.12
0.18
0.25
0.37
0.55
0.75
1.1
1.5
2.2
3
4
5.5
7.5
11
15
18.5
22
30
37
45
55
75
90
110
132
160
200
250
315
400
450
500
560
630

0.08
0.12
0.16
0.25
0.33
0.5
0.75
1
1.5
2
3
4
5.5
7.5
10
15
20
25
30
40
50
60
75
100
125
150
175
220
270
350
422
536
603
670
750
845

0.7
0.7
0.7
0.7
0.7
0.72
0.75
0.79
0.81
0.81
0.81
0.82
0.82
0.82
0.82
0.84
0.84
0.84
0.84
0.85
0.86
0.86
0.86
0.86
0.86
0.86
0.87
0.87
0.87
0.87
0.87
0.88
0.88
0.88
0.88
0.88

58
60
60
62
62
66
69
74
74
74
78
80
83
86
87
87
88
88
92
92
92
93
93
94
94
94
95
95
95
95
96
96
96
97
97
97

0.21
0.30
0.40
0.58
0.8
1.1
1.5
1.8
2.6
3.5
4.8
6.4
8.2
10.9
14.6
20.9
28.2
35
40
53
65
78
96
129
155
189
222
269
337
421
525
-
-
-
-
-

2
2
2
2
4
4
6
6
10
16
16
20
20
25
35
50
80
80
80
100
125
125
160
250
250
315
355
355
450
500
630
-
-
-
-
-

2
2
2
2
2
2
4
4
6
10
10
16
16
20
25
32
40
50
50
80
80
80
100
160
160
200
250
315
355
450
560
-
-
-
-
-

(Approximate figures for squirrel-cage motors).
Minimum fuse size for short-circuit protection of 3-phase motors.

The maximum size is determined by the requirements of the switchgear or overload relay
The rated motor currents are for standard 1500 r.p.m. 3-phase enclosed ventilated and totally enclosed fan-cooled motors.
D.O.L. starting : maximum starting current 6 x rated motor current. Maximum starting time : 5 s.
Y/D starting :     maximum starting current 2 x rated motor current. Maximum starting time : 15 s.
                            set overload relay in the phase lead to 0.58 x rated motor current.
Rated fuse currents for Y/D starting are also valid for 3-phase motors with slip-ring rotors.
For higher rated currents, starting currents / longer starting times, larger fuses will be required.
Table is valid for 'slow' / 'gL' fuses (DIN VDE 0636)
For NH fuses with aM characteristic, fuses = rated current selected.

 
Next >